 Bulletin 700S-CF
Industrial Relays
Overview/Product Selection Bulletin 700S-CF
* * * * IEC Industrial Safety Relay Positively Guided/Mechanically Linked Contacts as Per IEC 947-5-1 Annex L Third Party Certification By SUVA Red Cover and Mechanically Linked Contact Symbol on Front Face
Table Of Contents
Product Selection . . . . . . 197 Specifications . . . . . . . . . 199 Approximate Dimensions . . . . . . . . . . . 200
Type CF Safety Control Relays -- 8-Pole AC Voltage
AC-1 Ie [A] 40C 60C
AC-11 and AC-15 Ie [A] 24/48V 120V 240V 400V 500V 600V 690V
Connection Diagrams
Contacts Catalog Number N.O. N.C.
Main Contacts
Auxiliary Contacts
A1 K1 A2
13
21
33
43
53
61
71
81
4
54 62 72 82
4
700S-CF440C
Main Contacts
25
20
16
14
10
5
2.5
1.8
1
A1 K1 A2
14
22
34
44
13
21
33
43
53
61
71
83
5
14 22 34 44
3
700S-CF530C
54 53
62 61
72 73
84 83
Adder Deck Contacts
A1
13
21
33
43
10
6
6
6
3
2
2
1.2
0.7
K1 A2 14 22 34 44
6
54 62 74 84
2
700S-CF620C
All Cat. Nos. are factory-stocked.
AC Voltage Suffix Code
Voltage 50 Hz 60 Hz 50/60 Hz 12 R Q - 24 K J KJ 32 V - - 36 W V - 42 X - - 48 Y X KY 100 KP - KP 100110 - KP - 110 D - KD 120 P D - 127 S - - 200 KG - KG 200220 - KG - 208 - H - 208240 - L - 220230 F - -
Voltage 50 Hz 60 Hz 50/60 Hz
230 - - KF
230240 VA - -
240 T A KA
277 - T -
347 - I -
380 - E -
380400 N - -
400 - - KN
400415 G - -
440 B N KB
480 - B -
500 M - -
550 C - -
600 - C -
All Cat. Nos. are factory-stocked. See page 198 for coil voltage selection information.
197
Bulletin 700S-CF
Industrial Relays
Product Selection, Continued Ordering Details
Type CF Control Relays -- 8-Pole DC Voltage
DC-1 Ie [A]
DC-11 and DC-15 Ie [A] 240V 400V 500V 600V 690V
Connection Diagrams
Contacts
40C 60C 24/48V 120V
Main Contacts
A1 K1 A2 14 22
21
Auxiliary Contacts
21 33 43
53 61 71 81
Catalog Number N.O. N.C.
13
4
34
33
4
700S-CF440ZC
44
43
54
53
62
61
72
71
82
83
25
20
16
14
10
5
2.5
1.8
1
A1 K1 A2
13
5
14 13 22 21 34 33 44 43
3
700S-CF530ZC
54 53
62 61
72 73
84 83
A1 K1 A2
6
14 22 34 44
2
700S-CF620ZC
54
62
74
84
All Cat. Nos. are factory-stocked. See page 198 for coil voltage selection information.
DC Voltage Suffix Code
Voltage Standard With diode suppressor a
9 R -- 12 Q -- 24 J DJ 36 W -- 48 Y -- 60 Z -- 64 B -- 72 G -- 80 E -- 110 D -- 115 P -- 125 S -- 220 A -- 230 F -- 250 T --
When ordering DJ coil with built-in surge suppression, remove Z from the Cat. No. Example: Cat. No. 700S-CF440ZC becomes Catalog Number 700S-CF440DJC
Accessories
Safety Control Relays with Auxiliary contact block for side mounting 1- or 2-pole Electronic Timing Module on coil terminal side Mechanical Interlock on side of contactor Interface Module on coil terminal side Surge Suppressor on coil terminal side Labeling with label sheet marking tag sheet with clear cover marking tag adapter for System Bul. 1492W mm. a+9 b + 24 a+9 b+9 b+3 +0 +0 + 5.5 (inches) (a + 23/64) (b + 15/16) (a + 23/64) (b + 23/64) (b + 1/8) (+ 0) (+ 0) (+ 7/32)
198
Bulletin 700S-CF
Industrial Relays
Specifications General
Main Relay Cat. No. 700S-CF Contact Ratings -- NEMA Min. Contact Rating Contact Ratings -- IEC AC-15 (solenoids, contactors) at rated voltage IEC 947, EN 60947 Standard Gold 24V 48V 120V 240V 400V 480V/500V 600V 690V 40C Ith 230 V AC-12 (Control of resistive loads) IEC 60947 400 V 690 V 60C Ith 230V 400V 690V DC-12 Switching DC Loads
L/R
Front Adder Deck Contacts
Sidemounted Contacts Mechanical Life Electrical Life 6A 6A 6A 3A 2A 2A 1.2 A 0.7 A Terminal Size per IEC 947-1 Solid/Stranded 1 Conductor 2 Conductor Max. Wire Size per UL/CSA Tightening Torque Tightening Torque [mm2] [mm2] [AWG] [lb.-in.] [N*m] Terminal Type Weight AC-15 (240V, 3 A) AC Op. Mechanism [Mil] [Mil] [g]
Cat. No. 700S-CF 15 1.5 390
A600, P600
A600, Q600 20V, 10 mA 12V, 8 mA
Aux./Pneumatic Timer Contact (Frontmounted) 15 1.5 --
16 A 16 A 14 A 10 A 5A 2.5 A 1.8 A 1A 25 A 10 kW 17 kW 30 kW 20 A 8 kW 14 kW 24 kW
6A 6A 6A 5A 3A 1.6 A 1.2 A 1.0 A 10 A
Terminal Cross-Sections
2 x A4 1.5...6 1.5...6 16...10 8.9...22 1...2.5
2 x A4 0.5...2.5 0.75...2.5 18...14 8.9...13.3 1...1.5
6A
For 16 or more strands, end ferrule is required DC Switching Ratings for 700S-CF Main Poles in Series (Resistive Load at 60 C) 1 pole 24/48 V 25/20 A 6A 1.5 A 0.4 A 2 poles 25 A 25 A 8A 1A 3 poles 25 A 25 A 25 A 3A
< 1ms, Resistive Loads
24V 48V 110V 220V 440V
12 A 9A 3.5 A 0.55 A 0.2 A 5A 2A 0.7 A 0.25 A 0.12 A 0.14 A Yes 5A 2A 0.7 A 0.25 A 0.12 A 0.1 A Yes
12 A 9A 3.5 A 0.55 A 0.2 A 3A 1.5 A 0.6 A 0.3 A 0.2 A 0.1 A
125 V 220 V 440 V
IEC 60947
DC-13 IEC 60947, Solenoids and contactors
24V 48V 125V 220V 440V 660V
Location State of N.C. Contacts if N.O. contact welds of welded Front Left side Right side N.O. Main aux. aux. aux. contacts Main Positive ly Guided Contact s Front aux. Left side aux. Right side aux. Open Open Open Open Open Open Open Open Open Open
Open Open Open
Open
Open
Open
If the accessory is a pneumatic timer or latch, there is no positive guidance; the accessory contacts are independent. Defined in IEC 947-5-1 annex L. Positive guidance is a relationship between contacts of opposite types (i.e., N.O. and N.C.).
199
Bulletin 700S-CF
Industrial Relays
Approximate Dimensions
Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended for manufacturing purposes.
c2
c1 c
AC Safety Control Relays
a 45 (1-25/32) b 81 (3-3/16) c 119.5 (4-3/4) c1 114.5 (4-43/64) c2 6 (1/4) d 2 - 4.5 (2 - 3/16) d1 60 (2-23/64) d2 35 (1-25/64) Cat. No. 700S-CF
DC Safety Control Relays
a 45 (1-25/32) b 81 (3-3/16) c 145.5 (5-49/64) c1 140.5 (5-37/64) c2 6 (1/4) d 2 - 4.5 (2 -3/16) d1 60 (2-23/64) d2 35 (1-25/64) Cat. No. 700S-CF
Mounting Positions
Mounting Position
AC Safety Control Relays
DC Safety Control Relays
Safety Relay Circuit With 5 Safety Outputs
Use for E-stop control. E-stop will work properly if any one fault occurs (a fault could be one welded contact or one undesired open connection such as a loose wire). * High output switching capability and long contact life. * Circuit complies with EN 954 categories 1, 2, 3, 4 * Prevents restart of the 5 safety outputs if there is a single fault anywhere in the system. Use (3) 700S-CF relays and this diagram to construct the circuit, or contact your local Allen Bradley sales office for pre-assembled module *
200
Bulletin 700S-CF
Industrial Relays
Approximate Dimensions, Continued .
Basic Circuit (1) Output Circuit (3 Relays, 9 Terminal Blocks)
13
14
A1
A2
2 4 5 7 8 9 10 11 700S-CF 620* C
13
14
700-Z
33 34
Included in Factory Wired Units
21
22
21
22
A1
A2
1 3 5 7 8 9 10 11 700S-CF 350* C
61 62 43 44 A1 A2
4 6 7 8 9 10 11 700S-CF 620* C
13
14
33
34
21
22
33
34
LOAD 1
(5) Output Circuit (3 Relays, 17 Terminal Blocks)
14 15 16 17
43
18
44
19
51
52
20
43
44
21
LOAD 2
LOAD 3
53
22
54
23
61
62
24
53
54
25
73
26
74
27
71
72
28
63
64
29
LOAD 4 LOAD 5
83
84
81
82
73
74
Numbers shown are the line numbers where the contacts for this relay appear.
201


▲Up To Search▲   

 
Price & Availability of 700S-CF440XC

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X